Main Features
# FSK modulation with DSP technology
presents strong noise resistance. It ensures communication
capability even under heavy line loading conditions
# Carrier frequency band: 9 kHz ~ 95 kHz
(reserved for utility companies)
# Baud rate: 300 ~ 1200 bps
# Dual channel input enables the ability
to detect reverse rotation by sensor-type meter. This prevents
error arising from meter disc jittering motion.
# 15 pins single inline direct insertion
packaging, 38.1 x 19.05 mm.
# Unit can be easily installed into
electric meter by using mounting and power supply components
supplied by us.
# Calculation by time-of-use. The
time-of-use can be remotely set.
# When used with the full metering suite
from Archnet, the system can be used for line loss, phase balance
analysis and other management function.
# Bi-directional communication enables
overdue payment reminder and other similar functions.
Packaging structure

Pin Definitions
| No. |
1 |
2 |
3 |
4 |
5 |
6 |
7 |
8 |
9 |
10 |
11 |
12 |
13 |
14 |
15 |
| Pin |
NC |
NC |
NC |
TXD |
RXD |
NC |
T/R |
ARD |
CT |
IN1 |
TN2 |
Vcc |
GND |
Vss |
CR |
Pin Functions
NC:No connection
IN1:Pulse input 1
TXD:I/O port
IN2:Pulse input 2
RXD:I/O port
Vcc:+5 V power in
T/R:Signal transmit / receive control
Vss:-5V power in
ARD:Overdue payment signal out
GND:Ground
CT:Carrier signal out
CR:Carrier signal in
Our company provides software and system
development services including data communication protocol to
integrate the interface circuit into the meters. Your AMR systems
can be implemented with minimum effort.