Summary:
DT580 series 3-phase inductive long-life
active meters are manufactured according to the requirements of the
Mechanical & Electricity Ministry and meet the IEC521 standard.
Technical Specification:
¡ô Accuracy: class 1.0&2.0
¡ô Frequency:50Hz, 60Hz
¡ô Voltage:220-240V
¡ô Current(A): 1.5(6), 2.5(10), 5(20), 5(30),
10(40), 10(60), 15(60), 20(80), 30(100)
¡ô Driving torque:£¾8g.cm
¡ô Voltage power loss :£¼1w
¡ô Starting current:£¼0.5%Ib
Features:
¡ô Service life: not £¼25 years
¡ô Wide load: 4x-6x current load
¡ô Stable error curve
¡ô Low power loss
¡ô Anti-tamper protection:
1. Records forward and reverse accumulated
energy with anti-tamper reverse load protection.
2. The meter design features a back mounted
fastener which means the case must be broken if the meter is
tampered with.
3. An extended terminal cover prevents
external short circuit; if the neutral connection is removed load
current will not flow back to the meter.
¡ô Magnetic bearing: high sensitivity, high
stability and long life
¡ô The meter case is a strong polycarbonate
construction with high insulating properties
¡ô Meter reading system employs preset
impulse output
¡ô No adjustment for anti-creep hole
¡ô Voltage and current components are secured
using high accuracy rivet technology perfect conformability
¡ô Epoxy resin coated voltage coil provides
high insulation properties for 30 year even under adverse
environmental conditions
Materials:
¡ô Magnetic bearing:
1. Permanent coercive force ALNICO
magnetic-steel, stable magnetic process, high stability
2. Precision graphite sleeve, perfect
self-lubricating, low friction, wear resistance
¡ô Voltage and current sores are manufactured
from high quality and low linear loss silicon steel for
high-stability
¡ô Brake magnetic steel:
ALNICO37multi-pole,good stability
¡ô Low friction polyacetal drum register and
bearing bush, wear resistance, perfect self-lubricating.
|